Is it OK to have a 24 amp e18S or Liberty-Belle kiln on a 50 amp circuit?

  • This is fine to do if you are careful.
  • The only concern would be if you put the wrong elements in the kiln, or connected them to power incorrectly when you replace them.
  • If this happened, you would most likely ruin the inside of the kiln and possibly start a fire in the kiln's control box. This is because your circuit breaker and the copper wires to the outlet can accommodate a lot more power than the kiln wiring and components are designed to handle.